Similarly, what is knockout trade size?
A knockout for 1/2" conduit is 7/8", but the outside diameter of a 1/2" EMT fitting is about 3/4". 3/4" knockout is 1-3/32" (close enough to 1-1/8), and O.D. of 3/4" fitting is roughly 1".
One may also ask, what size hole saw do I need for 2 inch EMT? For 2 1/2″ conduit, drill using a 3″ hole saw or 2 1/2″ conduit knockout punch (2.914″ or 74mm). For 3″ conduit, drill using a 3 5/8″ hole saw or 3″ conduit knockout punch (3.539″ or 89.9mm).
Subsequently, one may also ask, what is the outside diameter of 3 inch EMT?
ACTUAL OUTER DIAMETER
| THIN WALL INCH SIZE (E.M.T.) | ACTUAL OUTSIDE DIAMETER | |
|---|---|---|
| 2 1/2" | = | 2.875" |
| 3" | = | 3.500" |
| 3 1/2" | = | 4.000" |
| 4" | = | 4.500" |
Is electrical conduit measured by ID or OD?
The ID and ODThere will also be a maximum OD. This is a fixed number that can not be deviated from. For instance, a 1-inch rigid conduit will have an ID of 1.063 inch nominal while a 1 inch intermediate metallic conduit will have an ID of 1.12 inch nominal, yet both have the same knockout size of 1.375 inches.